Carbon Dioxide:
Home > Products > Extinguishers > Types of Extinguishers > Carbon Dioxide

Carbon Dioxide

Typical Usages:
 
Carbon Dioxide or "CO2" extinguishers discharge a white cloud of carbon dioxide that smothers the fire by displacing the oxygen. You can recognize a CO2 fire extinguisher by its hard horn and lack of pressure gauge. It is designed for Class B — flammable liquids and Class C — electrically charge fires only. Because this type extinguisher displaces the oxygen, never use it in a confined space while people are present without proper respiratory protection. Carbon dioxide is a clean, non-contaminating, odorless gas frequently used in computer labs, mechanical rooms, and flammable liquid storage areas.

Sizes and Service Requirements:
 
Stored Pressure: - 5 lb., 10 lb., 15 lb., 20 lb
Maintenance: Monthly Inspection; Annual Maintenance; Annual Electrical Conductivity Test on Hose; and 5 yr. Hydrostatic Test
 
Wheeled Units: - 50 lb., 100 lb
Maintenance: Monthly Inspection; Annual Maintenance; Annual Electrical Conductivity Test on Hose; and 5 yr. Hydrostatic Test on cylinder and hose